MLV Sound Barrier + Fiberglass Acoustic Panels | Data Center Equipment Room, Dallas, USA

data center noise control

Project Overview A new modular data center in Dallas has multiple server equipment rooms and cold aisle containment zones. High-speed fans of servers and cooling units continuously generate strong mid-low frequency noise. Noise radiated outward affected adjacent office and monitoring rooms, and failed to meet local environmental noise limit. Space features high heat load and frequent air circulation; acoustic materials must be non-shedding, fire-safe and resistant to temperature fluctuation.

Solution Configuration Modular MLV damping sound barriers were arranged around cooling units and rack clusters, 3kg/㎡ high density, STC up to 27dB, blocking direct airborne noise radiation. High-density rigid fiberglass acoustic panels were installed on the inner wall and partial ceiling of equipment rooms to reduce reverberation inside the machine room and cut down reflected noise. Panels have hardened non-friable surface, no fiber falling off. All materials meet ASTM E84 Class A fire rating, suitable for long-term operation in hot airflow environment.

Project Result Noise level of the monitoring room adjacent to equipment room decreased by 39dB. Indoor reverberation of server room was effectively suppressed. Acoustic components kept stable performance after 24/7 continuous operation test. The project passed local environmental acceptance of industrial noise.